Reliable Telemetry & Logging via SMS & E-mail

Spider 2

A rugged datalogger and telemetry device designed for flexible monitoring, alarming, and reporting. Spider 2 succeeds the proven Spider SMS, bringing modern hardware, enhanced connectivity, and simple browser-based configuration.

Key Features

Comprehensive Sensor Support

Supports analogue, digital, and smart inputs—including voltage, 4–20 mA, state, switch, pulse, and Modbus—providing seamless integration with a wide range of industrial and environmental sensors.

Flexible Control & Automation

Onboard intelligence drives outputs by threshold, schedule, or remote command. Effortlessly control samplers, relays, pumps, lights, and sirens with minimal setup.

Seamless System Integration

Built-in Modbus/TCP and other industry-standard protocols ensure reliable connectivity with SCADA, BMS, and other digital modelling and control platforms.

Simple Setup & Management

No special software required—configure and monitor from any standard web browser, locally or remotely.

Scalable & Modular Deployment

A single Spider 2 can support 1,000s of points using wired and wireless modules. Designed for retail, high-rise, campuses, and industrial facilities.

Proven Low-Power Design

Optimised for mains or solar operation with integrated battery charging, delivering dependable long-term performance in remote or unattended locations.

How It Works

Deploy & Install

Connect analogue, digital, and Modbus sensors directly to Spider 2. Expand using Modbus and wireless network to collect data from over 1,000 remote meters and sensors.

Connect & Configure

Access the built-in web interface from any computer or mobile device. No software or licenses required—just a standard browser.

Automate Logging & Alerts

Set schedules, thresholds, or event triggers. Spider 2 automatically logs readings and sends SMS, secure email, or secure FTP reports. Alarms notify you instantly of abnormal events.

Monitor & Integrate

Access real-time and historical data via web browser. Compatible with SCADA, BMS, and other digital modelling and control platforms.

Applications

Building Automation

Research & Science

Government & Regulators

Simplify Your Monitoring

No complex software or specialised training required. Spider 2 provides a reliable, web-based solution for logging, alarming, and reporting, ready to integrate seamlessly with your existing systems.

Inputs & Outputs

Inputs
Integrated Inputs 8 × digital or analogue (voltage-free contacts, switches, pulse, open collector, meters, 0–2.4 V, 0–5 V, 0–10 V, 4–20 mA, common ground)
Wireless 400+ wireless inputs for metering
Modbus 900+ inputs (RS-485 or Ethernet)
System Internal temperature, charger state, battery voltage
Outputs
Total 8 outputs
Type Normally open latching relay contacts (1 A @ 30 V DC, resistive load)
Timers 8 (one per control)
Activation Local intelligence, timers, alarms, SMS, browser interface

Alarms & Communications

Alarms
Number of alarms 16
Type SMS + e-mail + voice
Trigger User definable input and trigger point
SMS / e-mail / voice message 1 per alarm, user definable
Number of phone numbers 3 per alarm, user definable
Number of e-mail addresses 2 per alarm, user definable
Communication Interfaces
Ethernet 100/10 base-T RJ-45
Mobile 4G LTE Cat 1, Wi-Fi
Antenna External
Internet connectivity 4G (modem type and network dependent)
RS-232 Serial Interface
RS-485 Multi-dropped, Multi-point Serial Interface

General

Physical
Size 110mm (W) × 200mm (H) × 85mm (D)
Weight ~800g
Material Custom plastic enclosure
Mounting Surface-mounted onto distribution board
Operating Temp -5°C to +50°C (-20 to +70°C on request)
IP Rating IP20
Warranty 12-month manufacturer's warranty
Logger
Capacity Approximately 100,000 records
Storage memory Battery backed RAM
Time resolution 1 second
Download format CSV file
Battery Charger
Built-in Sealed Lead Acid battery management system
External Input 16–30V DC
Peak Current 2A (when battery is discharged)
Input Current <120mA
Battery External 12V sealed lead-acid
Source Mains charger or solar panel